This comes up most often halfway through a kitchen refit, usually when someone realises the island they've designed has nowhere sensible to put an extractor. The question is whether a cooker hood is legally required, and the answer is more specific than either yes or no.
What the regulations require is extraction. A cooker hood is one way of achieving that, and not always the required one.
The Short Answer
Building Regulations Approved Document F covers ventilation, and it requires mechanical extraction in a kitchen at one of two rates: 30 litres per second if the extractor is sited over the hob, or 60 litres per second if it's elsewhere in the room. That's the rule, and it's about extraction capacity rather than the appliance providing it.
So a wall-mounted extractor fan meeting 60 l/s satisfies the requirement without any cooker hood at all. Equally, a beautiful chimney hood that only recirculates may not satisfy it, because recirculating units don't remove air from the building.
Crucially, this applies to new builds and to kitchens being newly created or substantially refitted where building control is involved. Simply replacing a broken cooker hood in an existing kitchen doesn't trigger anything. If you have no extraction now and you're not doing notifiable work, nobody is going to require you to install any.
What Actually Matters
The purpose behind Part F is not cooking smells. It's moisture.
Cooking releases a substantial amount of water vapour — boiling a pan of pasta puts well over a litre into the air. In a modern, well-sealed house with good insulation and double glazing, that moisture has nowhere to go. It condenses on the coldest surfaces available, which are usually window reveals, external wall corners and behind kitchen units.
That's how you get black mould in a kitchen corner, and it's why the regulations treat kitchen extraction as a health matter rather than a comfort one. The 30 and 60 l/s figures are derived from typical moisture generation rates, not from how strongly a kitchen smells of onions.
Understanding that changes how you read the rules. The reason a hood over the hob needs only half the extraction rate of one across the room is capture at source — it intercepts the plume before it disperses. A fan on the far wall has to change the air in the whole room to achieve the same result, hence double the rate.
Detailed Analysis
When the requirement actually bites
Part F applies when building work is carried out that falls under the regulations. In practice that means:
- New build properties. Always. Extraction to the stated rates is required and building control will check it.
- Extensions and conversions. A new kitchen in a loft conversion, garage conversion or extension needs compliant extraction.
- Changing a room's use to a kitchen. Turning a dining room into a kitchen creates a new "wet room" and triggers the requirement.
- Full kitchen refits where building control is notified. Often through electrical work under Part P, which can bring the ventilation into scope.
What it does not cover is swapping appliances in an existing kitchen, replacing units on the same layout, or living in a house that has never had extraction. Existing arrangements are generally left alone unless something triggers a fresh assessment.
This is where a lot of confusion comes from. Someone reads that extraction is a legal requirement, panics about their 1970s kitchen with an openable window and nothing else, and starts pricing up ducting they don't need.
Does a recirculating hood count?
This is the question that matters most in flats and island kitchens, and the honest answer is: generally not on its own.
Approved Document F is concerned with removing moist air from the dwelling. A recirculating hood filters grease and, via a carbon filter, some odour, then returns the same air — moisture included — to the room. From a ventilation standpoint it achieves very little.
In practice, building control officers vary in how they handle this, and some flats genuinely cannot be ducted. Where ducting is impossible, the usual route is a compliant extractor elsewhere in the kitchen, or a mechanical ventilation system serving the dwelling as a whole. It's worth raising with building control early rather than discovering it at sign-off.
Reading extraction rates on a spec sheet
Here's the trap. Manufacturers quote extraction in cubic metres per hour (m³/h). Regulations are in litres per second (l/s). The conversion is straightforward — divide m³/h by 3.6 to get l/s — but it lets a hood look far more capable than it is.
| Quoted m³/h | Equivalent l/s | Meets requirement? |
|---|---|---|
| 108 m³/h | 30 l/s | Bare minimum over the hob |
| 216 m³/h | 60 l/s | Minimum if sited away from the hob |
| 400 m³/h | 111 l/s | Comfortable for a typical kitchen |
| 700 m³/h | 194 l/s | Large or open-plan kitchens |
The second trap is that quoted figures are almost always free air — the hood running with no ducting attached. Once you add a duct run, bends and an external grille, real-world extraction can drop by 30 to 50 per cent. A hood quoted at 400 m³/h through five metres of flexible ducting with three bends may be delivering less than half that.
So specifying to the bare regulatory minimum is a mistake even when it technically complies. Aim for at least double the required figure on the spec sheet.
Gas hobs and the extra consideration
Where a gas hob is involved there's a second issue: combustion. Gas appliances consume oxygen and produce combustion products, and a powerful extractor in a sealed room can in principle pull flue gases back down an open-flued appliance elsewhere in the house — a boiler or a solid fuel stove.
This is why properties with open-flued appliances need adequate air supply, and why a very powerful extractor can require additional permanent ventilation. It's a Gas Safe matter rather than a Part F one, but it's part of the same conversation and worth flagging to whoever is doing the work.
Real-World Considerations
For rented property, the position is worth knowing. Landlords aren't required to retrofit extraction into a kitchen that never had it, but they are required to keep the property free from serious hazards under the Housing Health and Safety Rating System, and persistent damp and mould is one of those. A kitchen with no extraction and visible mould is a problem a landlord can be required to address, even though no specific hood is mandated.
For selling a house, extraction rarely appears in a standard survey unless there's visible damp. What does come up is unpermitted building work — an extension without sign-off, for instance — where ventilation may form part of a regularisation application.
The practical position for most people: if you're doing anything that involves building control, ask them directly at the start what they expect. Officers interpret Part F with some latitude, particularly on existing buildings, and a five-minute conversation early is worth considerably more than a compliance argument later.
And if you're simply wondering whether to fit one in a kitchen that has managed without: the regulations aren't the reason to. Condensation on the windows every time you cook, and mould appearing in the corner behind the units, are the reasons to.
Common Mistakes Buyers Make
Assuming a recirculating hood satisfies the regulation. It filters air; it doesn't remove it. In a notifiable project that distinction matters.
Specifying to the bare minimum figure. Quoted rates are free air. Real ducting loses a third to a half of it.
Confusing m³/h with l/s. They differ by a factor of 3.6, and it's easy to think a hood is four times more capable than it is.
Panicking about an existing kitchen. If you're not doing notifiable work, nothing requires you to retrofit extraction.
Forgetting the duct run when choosing a hood. A powerful hood on a long flexible duct with several bends underperforms a modest one on a short rigid run.
Alternatives Worth Considering
Where a hood over the hob isn't practical — islands, sloped ceilings, listed buildings — a venting hob draws steam downwards at the hob surface and ducts it away. Expensive, but it solves the sightline problem and can be specified as a ducted unit that satisfies the requirement properly.
A separate wall or ceiling extractor at 60 l/s is the cheaper route to compliance when the hob position makes a hood awkward. It's less effective at capturing cooking plumes, but it meets the rate and costs a fraction of an island hood.
For flats where external ducting is genuinely impossible, mechanical ventilation with heat recovery serving the whole dwelling is increasingly the answer in new developments, and it handles kitchen moisture as part of a wider system rather than appliance by appliance.
Frequently Asked Questions
Is an extractor fan a legal requirement in a UK kitchen?
Mechanical extraction is required in new builds and newly created or substantially refitted kitchens under Approved Document F — 30 l/s over the hob or 60 l/s elsewhere. Existing kitchens aren't required to be retrofitted.
Does a recirculating cooker hood meet building regulations?
Generally not on its own, because it returns moist air to the room rather than removing it. Where ducting is impossible, discuss alternatives with building control before committing.
What is 30 litres per second in m³/h?
108 m³/h. Multiply l/s by 3.6. Aim well above the minimum because quoted figures assume no ducting.
Do I need extraction if I only have an electric hob?
Yes — the requirement is about moisture, not combustion, so it applies regardless of hob type. Gas simply adds separate air supply considerations.
Can I just open a window instead?
Not for compliance in a notifiable project. Openable windows count as background ventilation and don't replace the mechanical extraction requirement.
Final Thoughts
The requirement is extraction at 30 or 60 litres per second depending on where it sits, not a cooker hood specifically, and it applies to new and substantially refitted kitchens rather than to every home in the country.
If you're mid-refit, convert the manufacturer's m³/h figure properly, specify well above the minimum to survive the duct run, and check with building control early if you're planning to recirculate. If you're just wondering about your existing kitchen, the regulations aren't asking anything of you — but the condensation on your windows might be.